How to Wire a 400XAC with 3-Phase 3-Wire Delta Input
How to wire a 400XAC with 3-Phase 3-Wire:
Input
460XAC Input
Phase | A-L | B-L | C-L | A-N | B-N | C-N | G |
1Ø2W | 10AWG (A-L/B-L/C-L short) | 10AWG (A-N/B-N/C-N short) | 12AWG | ||||
3Ø3W | 12AWG | 12AWG | 12AWG | A-L/A-N short | B-L/B-N short | C-L/C-N short | 10AWG |
3Ø4W | 16AWG | 16AWG | 16AWG | 10AWG (A-N/B-N/C-N short) | 10AWG |
Input | 430XAC | 460XAC |
Phase | 1Ø | 1Ø or 3Ø |
Voltage | 200~240 Vac±10% | 1Ø: 200-240 Vac±10% 3Ø3W: 200~240 Vac±10% 3Ø4W: 346-416 Vac±10% |
Frequency | 47 - 63 Hz |
8000 VA Input
- 240 3-Phase 3 wire service line
- 8000VA/240V = 33.333 Amps
- 33.333 Amps / 3 Phase = 11.11 Amps per Phase for 3 Phase 3 wires.
Country | Frequency | Configuration | Single Phase | Three Phase |
United States | 60 Hz | wye | 120/208 | 208 |
60 Hz | delta | 120/240 | 240 | |
60 Hz | 480 | |||
Canada | 60 Hz | delta | 120/240 | 240 |
60 Hz | wye | 575 |
6000 VA Input
- 0-300 V 3-Phase 4 wire output
- 2000 VA Max per phase
- 18.4 A Max per phase for voltage < 110 V
- 9.2 A Max per phase for voltage < 220 V
- 18.4 A * 110 V = 2024 VA or 9.2 A * 220 V = 2024 VA per Phase
- 2024 VA * 3 phase = 6072 VA